1. MAINTENANCE INSTRUCTIONS FOR POWER TRANSFORMERS
Maintenance Schedule
Sl
No
Inspection
frequency
Items to be
inspected
To be checked
Action required if
inspection shows
unsatisfactory
conditions
1 Hourly Ambient temperature
2 Hourly Winding
temperature
Ensure that temperature rise is
within specified limits.
3 Hourly Oil temperature
4 Hourly Load (amps)
Check against rated figures given
on the name plate
5 Hourly Voltage
6 Daily
Oil level in
transformer
Check oil level gauge
If low, top with dry
oil find whether there
is any leak.
7 Daily Oil level in bushing -- --
8 Daily Dehydrating breather
Check that air passages are free.
Check colour of active agent
If silicagel is pink,
change by new
charge. The old
charge may be
reactivated for using
again.
9 Daily
Oil level in OLTC
conservator
Check oil sight window or oil
level gauge
If low, top with new
dry oil
2. Sl
No
Inspection
frequency
Items to be
inspected
To be checked
Action required if
inspection shows
unsatisfactory
conditions
10 Daily
Relief diaphragm of
OLTC explosion
vent
--
Replace if cracked or
broken
11 Daily
Cooler fan, bearing
motor & operating
mechanism
Check the bearings. Examine
contacts, check manual control
and interlock
Lubricate the bearing.
Replace burnt or worn
contacts.
12 Quarterly
Bushings
Examine for cracks and dirt deposit
Clean the dirt. If
cracked or broken
replace the bushing.
13 Quarterly
Oil in transformer
Check for dielectric strength and
water content
Take suitable action
to restore quality of
oil.
14
Half yearly or
at the
end of 5000
operations
Oil in the diverter
switch of OLTC
a. Dielectric strength
Filter or replace if
BDV is less than
specified value.
b. Water content
Measure the water
content using KARL
FISHER method.
Replace/ recondition
if exceeds that limits
specified
15 Yearly Oil in transformer Check acidity resistivity, tan delta
and sludge
Filter or replace
16 Yearly
Oil filled condenser
bushing
Refer to the maintenance schedule
for OIP condenser bushings
As recommended
17 Yearly Gasket joints
Tighten the bolts
evenly to avoid
uneven pressure
3. Sl
No
Inspection
frequency
Items to be
inspected
To be checked
Action required if
inspection shows
unsatisfactory
conditions
18 Yearly Cable boxes Check sealing arrangements and
find out whether there is any leak
Replace gasket if
leaking
19 Yearly
Relays alarm and
other circuits
Examine relay and alarm contacts,
their operation fuses etc. check
relay accuracy.
Clean the components.
Replace contacts and
fuse if necessary
20 Yearly Painting
Rusting/colour
Touch up to be done
21 Yearly Earth resistance
--
Take suitable action if
earth resistance is
high
22
After 50000
operations of
the OLTC
Arcing contacts -- Replace if necessary
23 -do-
Lubricating oil in
the gear box of
driving
mechanism
Low oil level
Add or replace with
lubricating oil
24
5 yearly
1000 kVA to 2000
kVA
Overall inspection including core
and coil
Wash the core and
coils with clean oil
7 – 10
yearly
above 3000 kVA
Note :
In case of abnormal phenomena occurring during service, inform the manufacturer
the exact nature of the phenomena together with the name plate particulars for easy
identification.